6-36

Component Definition and Maintenance

7000L-UM300I-EN-P – June 2013

7000 “C” Frame




8. Per Figure 6.29, insert the hose plug on the hose barb of the

upper manifold. Insert a M10 bolt in the end of the chillblock
hose. Note that there may still be limited fluid leakage during
this procedure.

Figure 6.29 – Converter PowerCage Module (Service – per Step 8)



Shows flow plugs installed.


Repeat this procedure for the lower manifold connection point.

The chillblock can be extracted from the PowerCage per
“Instructions for removing Chillblock assembly”.