Analog outputs – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 343

Advertising
background image

Functional Description 5-35

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

Analog Outputs

A total of thirteen programmable analog outputs are provided on
various boards. There are two analog outputs on each SCB and 1 on
the CIB, which are intended for diagnostic purposes and are available
as test points for connection to an oscilloscope or chart recorder.
These analog outputs are 8-bit, non-isolated, with a range of -10V to
+10V. The CIB has one isolated 4-20mA or 0-20mA analog output
and 7 non-isolated analog outputs for connection to external devices
such as meters or isolation modules. The allocation of the analog
outputs is shown below:

No.

Output

Board

Description

1

Rect_TP1

SCBL

DAC_TP1

2

Rect_TP2

SCBL

DAC_TP2

3

Inv_TP1

SCBM

DAC_TP1

4

Inv_TP2

SCBM

DAC_TP2

5

Cib_TP4

CIB

CIB_TP4

6

4-20mA

CIB

Connector J4b

7

CIB_Port1

CIB

Connector J5b

8

CIB_Port2

CIB

Connector J5b

9

CIB_Port3

CIB

Connector J5b

10

Meter Port 1

CIB

Connector J9

11

Meter Port 2

CIB

Connector J9

12

Meter Port 3

CIB

Connector J9

13

Meter Port 4

CIB

Connector J9

Any parameter or variable can be assigned to any analog output. The
variables are scaled by using the corresponding scaling factor.

Advertising