1-10

Overview of Drive

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

Specifications

Description

NEMA

IEC

Power Rating (Liquid Cooled)

3000-9000 hp

2240-6715 kW

Motor Type

Induction or Synchronous

Input Voltage Rating

3300V , 4160V, 6600V, 6900V

Input Voltage Tolerance

± 10% of Nominal

Voltage Sag

-30%

Power Loss Ride-Through

5 Cycles (Std)

> 5 Cycles (Optional UPS)

Input Protection

Metal Oxide Varistor (MOV)

Input Frequency

50/60 Hz, +/- 5%

Input Short-circuit Current Withstand

5 Cycle

3300 V – 6000 V 

25 MVA RMS SYM

Basic Impulse Level

50 kV (0 – 1000 m)

Power Bus Design

Copper – Tin plated

Ground Bus

Copper – Tin plated 6 x 51 mm (¼ x 2 in.)

Customer Control Wire Way

Separate and Isolated

Input Power Circuit Protection

Vacuum Contactor with Fused Isolating Switch

or

Circuit Breaker

Input Impedance Device

Isolation Transformer or AC Line Reactor

Output Voltage

0 – 3300 V 

0 – 4160 V

0 – 6600 V

0 – 6900 V

Inverter Design

PWM

Inverter Switch

Symmetrical Gate Commutated Thyristor (SGCT)

Inverter Switch Failure Mode

Non-rupture, Non-arc

Inverter Switch Failure Rate (FIT)

100 per 1 Billion Hours Operation

Inverter Switch Cooling

Double Sided, Low Thermal Stress

Inverter Switching Frequency

420-540 Hz

Number of Inverter SGCTs

Voltage

SGCTs (per phase)

3300/4160 V
6600/6900 V

4
6

SGCT PIV Rating
(Peak Inverse Voltage)

Voltage

PIV

3300/4160 V
6600/6900 V

6500 V
6500 V

Rectifier Designs

18 Pulse

PWM (Active Front End)

Rectifier Switch

SCR (18 Pulse), SGCT (PWM Rectifier)

Rectifier Switch Failure Mode

Non-rupture, Non-arc

Rectifier Switch Failure Rate (FIT)

100 per 1 Billion Hours Operation

Rectifier Switch Cooling

Double Sided, Low Thermal Stress

Number of Rectifier Devices per phase

Voltage

18-Pulse

PWM

3300 V
4160 V
6600 V

6
6
6

4
4
6

SCR PIV Rating
(Peak Inverse Voltage)

Voltage

18-Pulse

PWM

3300 V
4160 V
6600 V

4500 V
4500 V
6500 V

6500 V
6500 V
6500 V

Output Waveform to Motor

Sinusoidal Current / Voltage

Medium Voltage Isolation

Fiber Optic

Modulation techniques

SHE (Selective Harmonic Elimination)

PWM (Pulse Width Modulation)

For 3300V designs, contact factory.

Short-circuit fault rating based on input protection device (contactor or circuit breaker)

BIL derating based on altitudes < 1000 m (3,300 ft.) Refer to factory for derating.