Troubleshooting

7-49

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Xfer Disable

345

Transfer Disabled-master only

– Transfer of master not allowed while

drive is stopping

XIO Card #1-6 Loss

81-86

An XIO card has dropped off the
communications link between the XIO cards
and the CIB.

– Reset the board in an attempt to re-

establish communications.

– Check all connections between the

Customer Interface Board and the

jumpers between individual adapters

– Verify the status of all XIO adapters by

comparing the LED status to the table in

the manual.

XIO Power Loss

108

The 24V to the XIO boards has dropped
below the set trip level, which is 95% of
rated voltage.

– Verify DC/DC power supply output
– Confirm wiring to the CIB from the

DC/DC Power Supply

– Check XIO LED status and compare to

values in the manual

Zero Slip

28

The value for Rated Motor RPM (P26) is the

same as speed calculated from Motor Poles
(P99) and Rated Motor Frequency (P29).

– Verify Rated Motor RPM is less than

synchronous speed