7-4

Troubleshooting

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Air Filter

73

The Pressure drop at the input to the
converter section sensed by the pressure
transducer (as a voltage) has dropped

below the value set in Pressure Value Trip
(P319). This is dependent on the operation
of the Main Cooling Fan.

– Verify fan rotation
– Check for blocked airflow in the filters/

heatsinks/ ducting (if installed) – Clean as
required

– Improper Trip settings – Verify Pressure

Value voltage level when running with
clear air flow, and compare to expected
values for that specific drive type

– Verify Alarm and Trip set-up procedure

was completed adequately and adjust as
necessary

– Verify for drives with external ducting that

there is sufficient air to the drive input

– Verify supply voltage to differential

pressure transducer, and confirm output is
stable

Auxiliary Prot’n

141

Standard External Fault/Warning Input
included to allow the end-user to install a
protective relay/system status contact that

can activate a drive fault or warning,
depending on configuration of Aux Prot
Class (P445)

Check device responsible for the

auxiliary contact to this input, and
investigate cause of the open contact
status

Check the 120V signal through the

external device

Check the XIO board inputs and

parameter status bits

Bad Reference

246

The CIB verifies a 2.5VDC reference in the
A-D converters during initial power up. If

this is missing, the A-D converters will not
respond as expected, and could cause
problems with functions including reference

commands

Cycle control power to see if fault still

exists (Note: It can be reset, as it is only
checked on initial power up: Resetting

the fault is NOT an indication the
problem is cleared

Replace CIB if fault persists

Cab Temp High

(C-Frame Only)

229

The drive has a temperature switch in
several cabinets, and all the N/C switches
are connected in series and fed back to the
XIO input. The levels are set differently for

different cabinets.

– Identify which switch has opened, and

focus on that cabinet

– Check for proper air flow within the

identified section

– Verify muffin fans are operating correctly
– Verify ambient temperature is within

tolerances

CIB A/Ds

240

CIB Hardware Fault

– CIB Hardware Problem
– Cycle control voltage to the drive, and if

the problem still exists the CIB board

should be replaced

CIB Time Base

239

CIB Hardware Fault

CIB Heartbeat

197

The heartbeat link between the CIB and the
DCB-L has been lost.

– Possible Failed CIB or DCB-L
– Check LED status and compare with

table in the manual

– Cycle control voltage to the boards, and

if the problem still exists replace the

CIB/DCB-L boards as necessary