7-10

Troubleshooting

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Gate Test Pwr On

196

The temporary power supply harness used
for Gating Tests on the SCR rectifiers has
not been removed from the DC/DC Power

Supply, and you have attempted to start the
drive.

– Remove the test harness from the drive

immediately after Gate Test is finished

– Verify fault detection wiring is per the

drawings, and measure the voltage on the

trip signals back to the CIB. The 5VDC is

supplied from the CIB to the fault circuit,

and is pulled low on the power supply

when healthy.

– Replace the DC/DC Power Supply if the

harness is removed and the fault can not
be cleared

GND Offset

245

CIB Hardware Fault

– CIB Hardware Problem
– Cycle control Power to the drive, and if

the problem still exists the board should

be replaced

Ground OC

173

The Ground Current measured on the
Ground Fault CT has exceeded the value in
Ground Fault Overcurrent Trip (P171) for
the duration set in Ground Fault Overcurrent

Delay (P172). The GFCT (Zero-Sequence
CT) is not installed in all drives.

– Verify the Burden resistor has not

opened

– Verify parameters are set properly
– Megger the drive and motor and input

transformer/AC line reactor to search for

a ground fault in the system

Input Prot’n #1

135

Standard External Fault/Warning Input
included to allow the end-user to install a

protective relay (IE Input Feed Protection
Relay) auxiliary contact that can activate a

drive fault or warning, depending on
configuration of InputProt1 Class (P440).

– Check device responsible for the

auxiliary contact to this input and

investigate the fault indicated by the
device‟s fault message

– Investigate internal and external causes

for this fault code

– Check the 120V signal through the

external device

– Check the XIO board inputs and

parameter status bits

InputProt’n #2

140

Standard External Fault/Warning Input
included to allow the end-user to install a
protective relay (IE Input Feed Protection

Relay) auxiliary contact that can activate a
drive fault or warning, depending on

configuration of InputProt2 Class (P444).

– Check device responsible for the

auxiliary contact to this input and
investigate the fault indicated by the
device‟s fault message

– Investigate internal and external causes

for this fault code

– Check the 120V signal through the

external device

– Check the XIO board inputs and

parameter status bits