Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 504

Advertising
background image

7-20

Troubleshooting

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

OutPut Open

43

DO or OP open fault

– Drive sees DO or OP contactor open.
– Check for open circuit at the drive output

PD Capcty Lo

47

Parallel Drive Capacity Low.
This is applicable to parallel drive only

– The available drive capacity is less than

50% of the motor rated current. The
drive cannot run.

Pressure Loss

(C-Frame Only)

223

The measured system pressure has
dropped below a preset trip level. The
standard operating pressure is around

50psi. The pressure switch is not designed
to be an accurate measure of pressure, but
is designed as a Pressure/No Pressure

indication. Typically anything less than
20psi will activate this switch.

– Check that the pumps are operating
– Verify that there are no leaks in the

system

– Verify that there is no blockage in the

system

Printer USART

242

CIB Hardware Fault

– CIB Hardware Problem
– Cycle control Power to the drive, and if

the problem still exists the board should
be replaced

Pump/Fan Pwr Off

(C-Frame Only)

230

The control power to the pumping system
and the heat exchanger fans is not present.

– Verify the disconnect switch is closed

and that there are no blown fuses

– Measure the voltage at the pump and fan

inputs to ensure voltage is present

– Trace the feedback to the drive from the

circuit, looking for loose wiring or

incorrect auxiliaries

R Neutral OC

206

Neutral Resistor Over Current.
This is applicable to Direct to Drive only

– Check the neutral R for open
– Check devices on rectifier and inverter

for short circuits

– Check the Line and Motor Filter

Capacitors for short between Phase-to-
Neutral or Phase-to-Phase. Refer to

Chapter 6 of the User‟s Manual for
detailed instructions on Testing Filter

Capacitors.

Rect Heatsink FO

198

While Not Running, the Fiber Optic signal
from the TFB on the Rectifier Heatsink,

connected to Channel A fiber optic receiver
RX7 on FOI-L-A is not present. This is only

a fault while not running. If this occurs while
running it will appear as a warning.

– Check TFB and FOI board for power

Check the Fiber Optic cables are

properly seated in the transmitters and
receivers

– Check the fiber optic cable for

kinks/bends/breaks that could be
blocking the signal

Rect Temp ChB FO

199

Not Normally Used: While Not Running, the
Fiber Optic signal from the optional TFB
connected to Channel B fiber optic receiver

RX7 on FOI-L-B is not present. This is only
a fault while not running. If this occurs while
running it will appear as a warning.

Rec HS Low Temp

204

If the measured temperature RHeatsink
Temp C (P254) is less than 2°C, and the

drive is not running, the drive will display this
fault.

– Verify that the ambient in the control

room is not below 2°C

– Verify power to the TFB

Advertising