Component Definition and Maintenance

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

Cooling System (cont.)

Cooling Circuit


This circuit is required to cool such devices as Silicon Controlled
Rectifier (SCR), Symmetrical Gate Commutated Thyristor (SGCT),
snubber resistors and sharing resistors. The SCRs and SGCTs are
positioned between two chill blocks in an alternating fashion to
create a horizontal stack. The sharing and snubber resistors on
mounted on a plate with cooling tubes embedded within. As cool
liquid flows through the cooling tubes the entire plate is cooled,
which in turn cools the resistors.

Chill Blocks


The chill blocks are constructed of highly conductive copper
machined parts that are silver soldered together. The parts are
machined to a fine surface finish. The copper chill block provides
good heat transfer from the electrical device to the chillblock. The
coolant system is connected to each chill block with flexible 10-mm
(3/8-in.) hose which fits onto stainless steel hose barbs which are
part of the chill block assembly.

Plate with Cooling Tubes

Chill Block

Coolant Hose

Figure 6.53 – Chill Block Assembly

Coolant Pumps


Two pumps (P1 and P2) are used to move coolant through the
system (Figure 6.54). One of the pumps is used as a backup. The
control logic alternates the primary and secondary pump once every
eight (8) hours. Ensure that the pumps never run dry, as this will
damage the pump seals. Ensure the pumps don‟t cavitate (pumping
air pockets) when filling the system.