Component Definition and Maintenance 6-121
7000 “C” Frame
7000L-UM300I-EN-P – June 2013
12. Press F3 [DATA] key. The cursor moves to the data field. In our
example we will enter 18 and then press Enter key.
13. Press F4 [RATE] key. The cursor moves to the rate field. Here
we will enter 0, which is the fastest sample rate (1 msec/sample)
and then press Enter key.
14. Press F5 [POST] key and enter 10 (this is the percentage of
post-trigger samples) and then press the Enter key.