Troubleshooting

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

2U1A Offline OC

366

6P or 18P SCR RECTIFIER FAULT

(Offline Open-Circuit)

For SCR rectifiers, this fault will occur after
the initial contact closure, or during the
diagnostic sequence after a start command.

After the Short-Circuit test described below,
the drive fires each device, and verifies that
the feedback from that device went low. If
the feedback does not go low, the drive
assumes the SCR must be Open-Circuited.

– Complete a resistance check on the

rectifier, including the gate-cathode
resistance, the snubber and sharing
resistors

– Complete a firing check on the rectifier
– Verify the snubber circuitry, and the

sharing resistors

– Verify fiber optic integrity from FOI board

transmitter to SCRGD board receiver

– Replace all faulty components

2U1B Offline OC

372

2U1C Offline OC

402

2U4A Offline OC

369

2U4B Offline OC

375

2U4C Offline OC

405

2V3A Offline OC

368

2V3B Offline OC

374

2V3C Offline OC

404

2V6A Offline OC

371

2V6B Offline OC

377

2V6C Offline OC

407

2W2A Offline OC

367

2W2B Offline OC

373

2W2C Offline OC

403

2W5A Offline OC

370

2W5B Offline OC

376

2W5C Offline OC

406

3U1B Offline OC

438

3U4B Offline OC

441

3V3B Offline OC

440

3V6B Offline OC

443

3W2B Offline OC

439

3W5B Offline OC

442

4U1C Offline OC

444

4U4C Offline OC

447

4V3C Offline OC

446

4V6C Offline OC

449

4W2C Offline OC

445

4W5C Offline OC

448