7-38

Troubleshooting

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

External 1-16

1-16

These are the optional additional External

Faults available when there is an additional
XIO board installed. This is configured with
XIO Ext Faults (P593), and this message
will appear if the specific input (1-16) is
configured in Fault Config as a Warning.

– See associated Fault Description

Fan On

30

The drive control is receiving a hardwired
fan feedback even though the fan has not

been commanded to run.

– Check Fan feedback wiring and confirm

with ED

Fan 1 Loss

31

Drives with a Redundant Fan (P141) will
give this warning if Fan 1 is running, there

were no problems with Fan 2, and Fan 1 is
lost. Fan 2 will start and the drive will

continue running.

– Investigate the cause of the Fan 1 loss

(OL / damaged relay)

– Verify Fan 2 is operating with the proper

current levels

– At the next possible shutdown, reset the

warnings and Fan 1 can be run again

Fan 2 Loss

32

Drives with a Redundant Fan (P141) will
give this warning if Fan 2 is running, there

were no problems with Fan 1, and Fan 2 is
lost. Fan 1 will start and the drive will
continue running.

– Investigate the cause of the Fan 2 loss

(OL / damaged relay)

– Verify Fan 1 is operating with the proper

current levels

– At the next possible shutdown, reset the

warnings and Fan 2 can be run again

Fan1 ContctrOpen

22

When the drive is running, the feedback
from the Fan 1 Contactor auxiliary and
Isolation Switch is lost, but the drive will not
trip and wait for Power Supply faults or Air

Pressure faults to fault the drive.

– If the drive faults, investigate problems

with the fan contactors or the fan
overloads

– If the drive is still running with this

warning, there is a problem with the
Fan Isolation Switch auxiliary

Fan2 ContctrOpen

199

When the drive is running, the feedback
from the Fan 2 Contactor auxiliary and

Isolation Switch is lost, but the drive will not
trip and wait for Power Supply faults or Air
Pressure faults to fault the drive.

Gate Test Pwr On

119

The gating harness is plugged into the
DC/DC power supply, and the drive has
detected some current flow

– This will occur whenever attempting a

gating test

– If there is no gating harness installed,

replace the DC/DC power supply

Gnrl IO Config

127

The XIO card which was being assigned to
the General I/O is not a card which can be

used for this purpose.

– Select the proper slot containing the XIO

card which is compatible for General I/O

usage using XIO General Input/Output
(P592)

Gnrl IO Conflict

128

The XIO card previously being used for
General I/O has been reassigned for
another purpose.

– Check the configuration of all XIO slots

using XIO General Input/Output (P592)
and XIO External Faults (P593), and

reassign if necessary.

Ground Differ

160

This represents an excessive difference

between the Analog and the Digital grounds,
measured on the CIB Board

– This could be a problem with the

grounding in the drive system

– Verify grounds are per the drawings
– Replace CIB to eliminate board as a

problem

– Contact Factory if problem persists