Component Definition and Maintenance 6-61

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

P1-AC input

PIN#

LABEL

1

EARTH

2

LINE 1

3

LINE 2

4

LINE 3

P2-DC output

PIN#

LABEL

1

+56V

2

+56V COMM

3

+56V

4

+56V COMM

P3-FAIL output

PIN#

LABEL

3

DC POWER FAIL (OUTPUT POWER GOOD)

14

AC/DC FAIL COMM (LOGIC RETURN)

15

CURRENT SHARING

16

AC POWER FAIL (POWER FAIL)




Ensure the output of the supply is 56V DC.

There is a potentiometer on the top of the power supply that adjusts
the 56 Volt DC output for the power supply. Isolate the output of
the power supplies; multiple supplies in series will affect your
measurements. With the control power on and the output of the
AC/DC Converter isolated from the drive control, adjust the
potentiometer until the output equals 56 volts DC. Perform this test
on each power supply. When all adjustments are complete, re-
connect the power supply to the circuit and re-measure the output.
Adjust if necessary.


If it is not possible to maintain 56 V DC, the power supply may be
faulty.