Component Definition and Maintenance 6-61
7000 “C” Frame
7000L-UM300I-EN-P – June 2013
P1-AC input
PIN#
LABEL
1
EARTH
2
LINE 1
3
LINE 2
4
LINE 3
P2-DC output
PIN#
LABEL
1
+56V
2
+56V COMM
3
+56V
4
+56V COMM
P3-FAIL output
PIN#
LABEL
3
DC POWER FAIL (OUTPUT POWER GOOD)
14
AC/DC FAIL COMM (LOGIC RETURN)
15
CURRENT SHARING
16
AC POWER FAIL (POWER FAIL)
Ensure the output of the supply is 56V DC.
There is a potentiometer on the top of the power supply that adjusts
the 56 Volt DC output for the power supply. Isolate the output of
the power supplies; multiple supplies in series will affect your
measurements. With the control power on and the output of the
AC/DC Converter isolated from the drive control, adjust the
potentiometer until the output equals 56 volts DC. Perform this test
on each power supply. When all adjustments are complete, re-
connect the power supply to the circuit and re-measure the output.
Adjust if necessary.
If it is not possible to maintain 56 V DC, the power supply may be
faulty.