Component Definition and Maintenance 6-137

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

Control Power Checks (No Medium Voltage)

 Apply 3 Phase Control power to the PF7000 drive, and test

power to all of the vacuum contactors (input, output, and bypass)
in the system, verifying all contactors can close and seal in.

 Refer to Publications 1502-UM050_-EN-P (Series D) and

1502-UM052_-EN-P (Series E) for a detailed description of
all contactor maintenance.

 Verify all single-phase cooling fans for operation.

 This includes the cooling fans in the AC/DC Power supplies

and the DC/DC converter.

 Verify the proper voltage levels at the CPT (if installed), AC/DC

Power Supplies, DC/DC converter, isolated gate power supply
boards.

 Refer to User Manual, Chapter 4 – Commissioning for

appropriate procedures/voltage levels for the above checks.

 Verify the proper gate pulse patterns using Gate Test Operating

Mode.

If

changes to the system have been made during the outage,

place the drive in System Test Operating Mode and verify all
functional changes.

Final Power Checks before Restarting

 Ensure all cabinets are cleared of tools, and all component

connections are back in place and in the running state.

 Put all equipment in the normal operating mode, and apply

medium voltage.

 If there were any input or output cables removed, verify the input

phasing, and bump the motor for rotation.

 If there were any changes to the motor, input transformer, or

associated cabling, you will have to retune the drive to the new
configuration using autotuning.

 Save all parameter changes (if any) to NVRAM.
 Run the application up to full speed/full load, or to customer

satisfaction.

 Capture the drive variables while running, in the highest access

level if possible.