4-66

Commissioning

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

Press EXIT [F10], go up to Parameters. Press
Enter, and then scroll down the list until you
reach Analog. Press Enter, and you will see
the same list of available ports and the
assigned parameter number, but not the name.


If you scroll down, you will reach the scaling
factors for the 4 Meter Port and the 3 CIB
Port outputs. All parameters are scaled to 0-
10V, with 0 representing the minimum value
given in Chapter 6 under Parameter
Descriptions, and 10V representing the
maximum value given in Chapter 6. These
Scaling parameters (ie Anlg Port2 Scle) can
be used to change the scaling.

Note: There are certain parameters whose minimum value is a negative number. In that

case, the minimum value of the parameter (-10V) is scaled to 0V output and the
maximum value is scaled to 10V output.


Highlight the appropriate Analog Scale
parameter and press Enter. You can enter
your new value, and then press Enter, and
EXIT (F10). Ensure you save to NVRAM
when you are finished.