6-12
Component Definition and Maintenance
7000L-UM300I-EN-P – June 2013
7000 “C” Frame
Capacitors
Reactor Transformer
Resistor Bank
Figure 6.9 – Location of Ground Filter in „C‟ Frame Drive
Loosen screws to
release capacitors
Remove screws for
replacing resistor bank
Important !
Torque on capacitor terminals
3,4 Nm (30 lb-in) maximum
Important!
Torque on resistor bank assembly
1,2 Nm (11.0 lb-in) maximum
Figure 6.10 – Torque Values for Ground Filter Assembly