Drive Installation

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

Red Plastic Housing

Window Area appears Blue

if subjected to shock

51 mm

(2.0)

21 mm

(0.8)

Figure 2.3 – Shock Indicator


Installation of Exhaust Air Hood


Even though this is a liquid-cooled drive, some sections still require
air circulation.

On the top of the cabinets with cooling fans, sheet metal exhaust
hoods are to be installed. The components to make up the exhaust
hood have been packaged and shipped with the drive and are to be
found in the control/cabling cabinet.


The first step is to remove the protective plate covering the fan
opening on the drive. It is a flat cover plate bolted to the top plate.
Remove the bolts and plate and set aside for re-use.


Secondly, loosely assemble the two L-shaped panel components
shipped with the drive.


NOTE: For PWM Rectifiers with a line reactor cabinet, there may
be a provision for small fans in the roof of the cabinet. This cabinet
will still have a full-size exhaust air hood.


Locate the exhaust hood on top of the cabinet per Figure 2.4 and re-
install the original cover plate previously set aside. (Care must be
taken that the notches on the bottom flange are oriented toward the
sides of the drive). Affix assembly to the drive top plate. Tighten all
hardware.