Component Definition and Maintenance 6-67

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

Pump Seal Replacement

A T T E N T I O N

A T T E N T I O N

Do not run the pumps without coolant. Ensure
coolant is present in the system. Damage to the
pump seals may result.


Isolate the pump by closing valve V4 and V11 or V5 and V12. Note
that the non-return valve NV1 or NV2 will stop coolant from flowing
back to the pump being serviced. Follow the pump seal replacement
instructions from the pump manufacturer.


Refer to pump nameplate for manufacturer‟s model information.
Typical pump seal replacement information is provided at
www.goulds.com/pdf/SST-C,SST-F%20IOM.pdf

V11

P1

P2

V5

V12

V4

Figure 6.54 – Drain/Fill Pump