7-32

Troubleshooting

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

WARNING MESSAGES

WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

AC/DC#1 DC Fail

95

The output of the specified AC/DC Power
Supply has seen the 56VDC output voltage

drop below the hardwired trip level. The trip
level is fixed in hardware as 52VDC ±
1.7VDC, depending on hardware tolerances.

All of the outputs of the optional multiple
AC/DC power supplies are individually
monitored and displayed separately. THIS

WILL ONLY APPEAR IF YOU HAVE A
REDUNDANT POWER SUPPLY.

– Measure the input voltage and verify it is

within limits

– Measure the output voltage and confirm

whether the output level indeed falls below

the trip level

– Verify fault detection wiring is per the

drawings, and measure the voltage on the

trip signals back to the CIB. The 5VDC is

supplied from the CIB to the fault circuit,

and is pulled low on the power supply

when healthy.

– Verify the internal cooling fan is

operational

– Replace the Power Supply if required

AC/DC#2 DC Fail

96

AC/DC#3 DC Fail

97

AC/DC#4 DC Fail

98

AC/DC#5 DC Fail

99

AC/DC#6 DC Fail

100

AC300 AC Fail

103

The AC Fail signal from the 300W AC/DC

power supplies has been activated. This is
treated as a warning since a real loss of this

input voltage will result in a subsequent DC
fail signal. This happens at 85VAC.

– Investigate possibility of loss of input

voltage to the AC/DC Power Supply

– Verify output voltage
– Check alarm signal connections
– Replace Power Supply if necessary.

AC/DC PS AC Fail

102

The AC Fail signal from the 1500W AC/DC

power supplies has been activated. We
treat this as a warning since a real loss of

this input voltage will result in a subsequent
DC fail signal. This will occur at 127VAC L-
L for 3-phase supplies, and 90VAC for
single-phase supplies.

– Investigate possibility of loss of input

voltage to the AC/DC Power Supply

– Verify output voltage
– Check alarm signal connections
– Replace Power Supply if necessary.

Adapter 1 Loss

175

There has been a loss of communication
between the CIB and the identified
SCANport Adapter (Polled Communication).

This will appear as a warning in the drive
when the associated bits in Adapter Loss
Mask (P175) are set to a 0.

– Ensure that the SCANport device is

powered

– Verify the SCANport light status and

ensure the device is operating properly

– Verify the customer SCANport network

is properly communicated with the device

– Check CIB LED status
– Cycle control power to the drive
– Change the adapter if all attempts to

restore communication fail

Adapter 2 Loss

176

Adapter 3 Loss

177

Adapter 4 Loss

178

Adapter 5 Loss

179

Adapter 6 Loss

180