Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 299

Advertising
background image

4-94

Commissioning

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

4. Adjust the reference command to a value around the middle of

the operating speed range.


5. Start the drive and wait for it to accelerate to the commanded

speed.


6. Set parameter "Speed ref step" in "Speed Control" to 0.8 Hz.

The drive speed will step up and down by this amount at regular
intervals. The step of 0.8 Hz corresponds to 4 V on the test point.
Since the speed error signal has a range of only 4 Hz in order to
achieve the required resolution for small changes in speed, the
signal may sometimes rollover (jump from +10V to -10V)
during the speed step. If this occurs, it can be eliminated by
adjusting the reference command up or down slightly.


7. Adjust the value of parameter "Total inertia" until the speed rises

to approximately 63% of its final value in 1 second as shown in
the figure. If the response time is too fast, it indicates that “Total
inertia” is set too high and should be decreased. If the response
is too slow, then “Total inertia” is set too low and should be
increased.

CORRECTLY TUNED SPEED REGULATOR



8. Set parameter "Spdreg bandwidth" to the normal operating value.

Confirm that the response time is equal to the inverse of the
speed regulator bandwidth and that there is minimal overshoot.
For example, if the speed regulator bandwidth is set to 2 rad/sec,
the speed should rise to 63% of its final value in 0.5 second.


9. Set parameter "Speed ref step" to zero and stop the drive.

Advertising