Pump maintenance and replacement (cont.) – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 422

Advertising
background image

6-78

Component Definition and Maintenance

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

Strainers


Cleaning the Strainer

1. Open valve V1, shown in Figure 6.63, to ensure flow to the

pumps.

2. Close valve V2 and V3. Loosen strainer by hand. Clean it

properly in water and dry it before putting it back.

3. Open V2 and V3 slowly to avoid a rush of air into the pumps.

The air will gradually be purged from the system by flowing
through the reservoir.

4. Close valve V1.

To Pump P2

V1

V3

Strainer
STR1

V2

To Pump P1

Figure 6.63 – Cleaning the Strainer

Pump Maintenance and

Replacement (cont.)

Advertising