Troubleshooting

7-45

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Parameter Range

88

A parameter was read from NVRAM or the
DIM, which was outside the valid range.
The parameter has been set to a default

value. The Linear # of this parameter has
been stored in "Parameter Error", under the
Feedback grouping.

– If this was a result of an INIT operation,

contact the factory

– If this was a result of a LOAD operation,

correct the parameter value and perform

a SAVE operation

– Check the settings on the DIM to

determine whether it is limiting the

paramter‟s max or min values.

Phantom Alarm

93

DEVELOPMENT ERROR - An unused bit in

the last 16 bits in either a fault or warning
word has been set and detected by the
Alarm Queue server. These bits are never
used in firmware. Either a used bit has
been overlooked in the Faults/Warnings
database, or the control is incorrectly setting

an alarm word.

– Noise/Grounding Issue
– Contact the factory

Pump Failure

(C-FRAME ONLY)

143

The drive has detected a fault from one of
the pumps in the cooling circuit.

– Verify the Pump O/L settings and

conditions

– Verify the Pump Control Relay status

and auxiliary contact signals.

Queues Cleared

91

This means that the drive had to clear the
fault and warning queues after an upgrade
of the firmware

– This was an issue because the memory

structure changed in 3.xxx firmware

– No action is required

R Stator High

52

Autotune Rs (P219) measured during the
autotune test was higher than 0.20 pu,
indicating the presence of extremely long

motor leads.

– REFER TO THE POWERFLEX 7000

SERIES B MANUAL (CHAPTER 4 –
COMMISSIONING) ON AUTOTUNE

PROCEDURES, RESULTS, AND
ACTIONS

– Ensure motor windings are connected

properly.

Rec Gate Pwr

205

Rectifier Gate driver power supply warning

– The device feedback was not correct due

to power loss to the gate driver board.

– This can be from the 20V DC output of the

IGDPS or on the gate driver board itself.

– This warning can also appear as a result of

another device fault such as an Online

Fault.

Rec Heatsink FO

203

While Not Running, the Fiber Optic signal
from the TFB on the Rectifier Heatsink,

connected to Channel A fiber optic receiver
RX7 on FOI-L-A is not present. This is only
a fault while not running. If this occurs while
running it will appear as a warning.

– Check TFB and FOI board for power
– Check the Fiber Optic cables are properly

seated in the transmitters and receivers

– Check the fiber optic cable for kinks, bends,

breaks that could be blocking the signal

– This can occur if the sensor is not

connected to the TFB
NOTE: This is a warning because the

drive should not fault on the loss of the
signal while running. There is no
imminent danger to the drive, but the
user needs to be aware that there is a
temperature feedback signal missing.

Rec ChannelB FO

204

Not Normally Used: While Not Running, the

Fiber Optic signal from the optional TFB
connected to Channel B fiber optic receiver
RX7 on FOI-L-B is not present. This is only
a fault while not running. If this occurs while
running it will appear as a warning.