WARNING

MESSAGE

WARNING

CODE

DESCRIPTION

RECOMMENDED ACTIONS

U1A Device Wrn

228

INVERTER SGCT WARNING

FOR REDUNDANT DEVICES or N-1
CAPABILITY ONLY

This warning will only occur during the initial
contactor closure and the diagnostic

sequence after a start command. The
inverter monitors the state of the feedback
before a gate pulse is given, and monitors

the feedback after a gate pulse has been
sent. The SGCT has smart diagnostics, so
the feedback may indicate short before

firing, and if the pulse is received and the
device is really shorted, the diagnostic will

toggle the feedback to let you know the
problem is with the device, or the power
supply for that device.

The firmware now completes a diagnostics

sequence immediately after any drive reset,
with the goal of detecting problems before
any destructive action is taken from the next
action

– Complete a resistance check per the

instructions in the manual

– NOTE: SGCTs may not have completely

shorted, and still could read in the kΩ

range – Any devices with low suspect
readings should be changed in matched

sets during the next outage

– Check the LED status of the SCGT gate

driver card for abnormal readings

– Complete a Gating Test mode check on

the devices

– Verify the associated 20V power supply

is powered and active

– Verify all the power connections to the

SCGT firing card are seated properly

– NOTE: For Redundant devices, there

will be no change in the drive operation.
For N-1 drives, the drive will attempt to

run at a load/speed combination that
does not exceed the voltage rating of the
remaining devices.

U1B Device Wrn

234

U1C Device Wrn

246

U4A Device Wrn

231

U4B Device Wrn

237

U4C Device Wrn

249

V3A Device Wrn

230

V3B Device Wrn

236

V3C Device Wrn

242

V6A Device Wrn

233

V6B Device Wrn

239

V6C Device Wrn

251

W2A Device Wrn

229

W2B Device Wrn

235

W2C Device Wrn

247

W5A Device Wrn

232

W5B Device Wrn

238

W5C Device Wrn

250

U1A Online Wrn

216

INVERTER SGCT WARNING

FOR REDUNDANT DEVICES or N-1
CAPABILITY ONLY

This warning will occur during operation of
the drive. The drive has detected that the
feedback from the device was not correct,

and does not wait to determine the exact
problem. The drive polls the entire bridge 3
times before and 3 times after each gating

command. All 6 of these readings for each
device must be consistent for the warning to

occur. There is also a parameter called
Inverter Device Diagnostic Delay (P268),
which allows you to change the number of

consecutive firings to eliminate nuisance
faults. It will still poll 3 times before and

after each firing, but will now require the
condition to exist for the number of
consecutive firings set in the Diagnostic

Delay parameter for a warning to occur.

The firmware now completes a diagnostics
sequence immediately after any drive reset,
with the goal of detecting faults before any
destructive action is taken from the next
action

– Complete a resistance check per the

instructions in the manual

– NOTE: SGCTs may not have completely

shorted, and still could read in the kΩ
range – Any devices with low suspect
readings should be changed

– Check the LED status of the SCGT gate

driver card for abnormal readings

– Complete a Gating Test mode check on

the devices

– Verify the associated 20V power supply

is powered and active

– Verify all the power connections to the

SCGT firing card are seated properly

– For nuisance faults, contact the factory

about extending the Diagnostic Delay

– NOTE: For Redundant devices, there

will be no change in the drive operation.
For N-1 drives, the drive will attempt to
run at a load/speed combination that

does not exceed the voltage rating of the
remaining devices.

U1B Online Wrn

222

U1C Online Wrn

240

U4A Online Wrn

219

U4B Online Wrn

225

U4C Online Wrn

243

V3A Online Wrn

218

V3B Online Wrn

224

V3C Online Wrn

242

V6A Online Wrn

221

V6B Online Wrn

227

V6C Online Wrn

245

W2A Online Wrn

217

W2B Online Wrn

223

W2C Online Wrn

241

W5A Online Wrn

220

W5B Online Wrn

226

W5C Online Wrn

244

Advertising