Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 487

Advertising
background image

Troubleshooting

7-3

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

FAULT MESSAGES

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

AC/DC#1 DC Fail

143

The output of the specified AC/DC Power
Supply has seen the 56VDC output voltage

drop below the hardwired trip level. The trip
level is fixed in hardware as 52VDC ±

1.7VDC, depending on hardware
tolerances.. All of the outputs of the optional
multiple AC/DC power supplies are

individually monitored and displayed
separately.

– Measure the input voltage and verify it is

within limits

– Measure the output voltage and confirm

whether the output level indeed falls below

the trip level

– Verify fault detection wiring is per the

drawings, and measure the voltage on the

trip signals back to the CIB. The 5VDC is

supplied from the CIB to the fault circuit,

and is pulled low on the power supply

when healthy.

– Verify the internal cooling fan is

operational

– Replace the Power Supply if required

AC/DC#2 DC Fail

144

AC/DC#3 DC Fail

145

AC/DC#4 DC Fail

146

AC/DC#5 DC Fail

147

AC/DC#6 DC Fail

148

AC300 DC Fail

153

Optional for drives with an internal or

external UPS option – The 300W AC/DC
converter specially fed by the UPS has seen
the 56VDC output voltage drop below the

hardwired trip level. The trip level is fixed in
hardware as 51.5VDC ± 1.4VDC,
depending on hardware tolerances.

– Measure the input voltage and verify it is

within limits

– Measure the output voltage and confirm

whether the output level indeed falls below

the trip level

– Verify fault detection wiring is per the

drawings, and measure the voltage on the

trip signals back to the CIB. The 5VDC is

supplied from the CIB to the fault circuit,

and is pulled low on the power supply

when healthy.

– Replace the Power Supply if required

Adapter 1 Loss

309

There has been a loss of communication

between the CIB and the identified
SCANport Adapter (Polled Communication).
The drive will configure the specific Adapter

Loss 1-6 as a fault when the associated bits
in Adapter Loss Mask (P175) is set to a 1.

– Ensure that the SCANport device is

powered

– Verify the SCANport light status and

ensure the device is operating properly

– Verify the customer SCANport network is

properly communicated with the device

– Check CIB LED MOD A status
– Cycle control power to the drive
– Change the Adapter and/or CIB if all

attempts to restore communication fail

Adapter 2 Loss

310

Adapter 3 Loss

311

Adapter 4 Loss

312

Adapter 5 Loss

313

Adapter 6 Loss

314

Adaptr1 ForceFlt

129

There has been a loss of communication
between the identified DPI adapter and the
customer‟s communication network. The

communication between the drive and the
DPI adapter may still be active. This is a
requirement for DPI communications. If the

loss of communication from the network to
the adapter is required to be a warning, this

must be set in the adapter itself, not within
the drive.

– Verify the adapter LED status and ensure

the device is operating properly

– Verify the customer network is properly

communicated with the device

– Check CIB LED status and compare to

the information in Chapter 6 of the User‟s
Manual

– Change the Adapter if all attempts to

restore communication fail

Adaptr2 ForceFlt

130

Adaptr3 ForceFlt

131

Adaptr4 ForceFlt

132

Adaptr5 ForceFlt

133

Adaptr6 ForceFlt

134