6-44

Component Definition and Maintenance

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

Sharing Resistors (cont.)

SCR PowerCages


To obtain the sharing resistor value, disconnect the 2-pole plug of the
self-powered gate driver board labeled SHARING and SNUBBER
on the circuit board. The red wire of the plug is the sharing resistor.
Measure the resistance between the red wire of the plug and the chill
block to the left (the anode chill block). A value of approximately
80 k

Ω indicates a healthy sharing resistor.

Anode

Chillblock

Cathode

Chilblock

Disconnect Points

Rsh-1

Rsn -1

Cs-1

Cs-2

Rsn -2

To Gate Driver Board

TP

Rsh-2

Figure 6.35 – SCR PowerCage Snubber Circuit Connections



In the liquid cooled drive the sharing and snubber resistors can be
replaced independently. The sharing resistor is located in the same
spot on every chill block assembly, and the number of snubber
resistors can vary with the drive rating. The snubber and sharing
resistors are part of the chill block assembly. Servicing of resistors
requires that the chill block be removed from the PowerCage. See
“Chill block Removal and Replacement”.

1. Remove the chill block outlined in “Chill Block Removal and

Replacement”

2. Note all connections for correct replacement.

Snubber and Sharing

Resistor Replacement