Hall effect sensor replacement – Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 358

Advertising
background image

6-14

Component Definition and Maintenance

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

1. Ensure there is no power to the equipment.

A T T E N T I O N

A T T E N T I O N

To prevent electrical shock, ensure the main
power has been disconnected before working on
the Hall Effect sensor. Verify that all circuits are
voltage free using a hot stick or appropriate
voltage-measuring device. Failure to do so may
result in injury or death.

2. Note the location of all wires and the orientation of the Hall

Effect sensor. For quick reference, look for the white arrow
when checking the orientation of the Hall Effect sensor, look for
the white arrow.

I M P O R T A N T

I M P O R T A N T

The Hall Effect sensor and wires must be in the
proper orientation. Note the position before
disassembly.

3. The round bus bar must be removed. Remove the M10 hardware

and slide the bar out.

4. Remove the screws from the three terminals to allow removal of

the ring lugs.

5. Remove the four screws on the base of the Hall Effect sensor.

6. Replace the Hall Effect sensor. Note the arrow must be oriented

as shown in the illustration below.

7. Slide the bus bar back into place and secure with the M10 hardware.

8. Fasten the ring lugs on the wires back into place in the correct

position. Do not overtighten or you will break the threaded stud.

Customer Terminals

Hall Effect
Sensors

Figure 6.12 – Motor Terminal Assemblies

Note: Arrows on Hall Effect sensors indicate direction of current
flow. Customer Terminals shown for bottom cable entry. Customer
must remove and re-orient terminals if top entry is required.

Hall Effect Sensor

Replacement

Advertising