Drive Installation 2-5

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

Storage

If it is necessary to store the drive, be certain to store in a clean dry
dust free area.

Storage temperature should be maintained between -20°C and 65°C
(-4°F and 149°F). If storage temperature fluctuates or if humidity
exceeds 85%, space heaters should be used to prevent condensation.
The drive should be stored in a heated building having adequate air
circulation. The drive must never be stored outdoors.


Siting of the Drive

Site Considerations

The standard environment in which the equipment is designed to
operate is:

• Elevation above sea level less than 1000 meters (3250 feet)

• Ambient air temperature between 0°C (32°F) and 40°C (104°F)

• Relative humidity of the air not to exceed 95% non-condensing


For the equipment to operate in conditions other than those specified
consult the local Rockwell Automation Sales office.


The equipment requires the following site conditions:

(A) Indoor installation only, no dripping water or other fluids

(B) Clean air for cooling requirements

(C) Level floor for anchoring the equipment. Refer to dimension

drawings for the location of the anchoring points.

(D) The room in which the equipment is located must allow for full

opening of the doors of the equipment, typically 1200 mm
(48 inches). Also, allowances have to be made for clearance
for fan removal. This fan allowance must be greater than 700
mm (27.5 inches).

or

Dimension drawings can be obtained by contacting the local
Rockwell Automation Sales office. The equipment does not
require rear access for servicing.

(E) Allowance must be made for the stream of cooling air that

exits the drive at the top. The flow of cooling air into and out
the drive must be kept clear and uninhibited.