Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual
Page 483

Component Definition and Maintenance 6-139
7000 “C” Frame
7000L-UM300I-EN-P – June 2013
Time Estimations
Operational Maintenance
Changing DI Cartridge
0.5 hours
Cleaning/Changing both Mesh Filters 0.5 hours
Pump maintenance
0.5 hours
Annual Maintenance
Initial Information Gathering
0.5 hours
Physical Checks
– Torque Checks
2.0 hours
– Inspection
2.0 hours
– Cleaning **
2.5 hours **
– Meggering
1.5 hours
Control Power Checks
– Contactor Adjustments **
2.0 hours **
– Voltage Level Checks
1.0 hours
– Firing Check
0.5 hours
– System Test **
2.0 hours **
Medium Voltage Checks
– Final Inspection
0.5 hours
– Phasing Check **
1.5 hours **
– Autotuning**
2.0 hours **
– Operation to Maximum Load
Site Dependent
Additional Tasks
– Investigation **
Depends on Nature of the Problem **
– Informal Training/Refresher **
2.0 hours **
– Spare Parts Analysis **
1.0 hours **
– Vacuum Bottle Integrity Check ** 3.0 hours **
Final Report
3.0 hours
Note: ** indicates that the time may not be required depending on
the nature of the maintenance and the condition of the drive system.
These times are only estimations.