Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 499

Advertising
background image

Troubleshooting

7-15

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

Line FOB ChA PS

214

The 5VDC power supply to the Line Fiber
Optic Interface Board A from the Line DCB
is not present.

– Bad 5VDC supply – Check the 5VDC

test point on the DCB-L

– Verify LED status on the FOI Board
– Check all the pins that mount the FOI

board to the DCB and ensure none are
bent/broken

Line FOB ChB PS

215

The 5VDC power supply to the Line Fiber
Optic Interface Board B from the Line DCB

is not present.

Line FOB ChC PS

216

The 5VDC power supply to the Line Fiber
Optic Interface Board C from the Line DCB
is not present.

Master CurrentUB

163

The measured and calculated phase
currents in the Master Bridge have
exceeded the value set in Line Current
Unbalance Trip (P108) for the duration set in
Line Current Unbalance Delay (P109).

– Verify that all Current Transformer

connections are connected properly and
that no wires are reversed – Ring-out
wires to verify connections

– Check grounding on CTs
– Ensure that all plugs are firmly

connected in the SCBL

– Check that all input voltages are

balanced

– Verify Parameter settings
– Check the burden resistors
– Verify the Input Capacitor values if

installed

– Verity that there are no open sharing

resistors.

– Verify all Line Thyristors are firing in

Gating Test Mode

– Check the Line Filter Capacitors (for

PWM rectifier drives). Refer to Chapter 6

of the user manual for detailed
instructions on Testing Filter Capacitors.

Master VoltageUB

160

The measured phase voltages in the Master
Bridge have exceeded the value set in Line
Voltage Unbalance Trip (P271) for the

duration set in Line Voltage Unbalance
Delay (P272).

– CHECK TSN FUSING
– Verify the VSB connections and tap

settings, and check resistance of VSB
board – Megger board to confirm integrity

– Check actual voltage values on the

Operator Interface terminal for each
bridge and the total line voltage

– Check for possible source voltage supply

problems

– Use Multimeter and Oscilloscope to

check voltages on the drive voltage test
points

Advertising