Component Definition and Maintenance 6-11
7000 “C” Frame
7000L-UM300I-EN-P – June 2013
2. Note the position of the leads.
3. Remove the 6.4-mm (¼ inch) hardware and disconnect the leads
connected to the terminals.
4. Four brackets are used to secure the capacitor. Loosen the four
screws at the base of the brackets and lift the capacitor out.
5. Place the new capacitor and tighten the screws securely.
6. Replace the ring lugs and 6.4-mm (¼ inch) hardware.
(See Figure 6.8)
I M P O R T A N T
I M P O R T A N T
The maximum torque for the capacitor terminal
is 3.4 N-m (30 lb-in)
Loosen screws to release capacitor
Important !
Torque on capacitor terminals
3.4 N-m (30 lb-in)
Figure 6.8 – Capacitor in Grounding Network