background image

Component Definition and Maintenance 6-11

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

2. Note the position of the leads.

3. Remove the 6.4-mm (¼ inch) hardware and disconnect the leads

connected to the terminals.

4. Four brackets are used to secure the capacitor. Loosen the four

screws at the base of the brackets and lift the capacitor out.

5. Place the new capacitor and tighten the screws securely.

6. Replace the ring lugs and 6.4-mm (¼ inch) hardware.

(See Figure 6.8)

I M P O R T A N T

I M P O R T A N T

The maximum torque for the capacitor terminal
is 3.4 N-m (30 lb-in)


Loosen screws to release capacitor

Important !
Torque on capacitor terminals

3.4 N-m (30 lb-in)

Figure 6.8 – Capacitor in Grounding Network