Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual
Page 245

4-40
Commissioning
7000L-UM300I-EN-P – June 2013
7000 “C” Frame
Snubber Capacitance (SCR Device)
Turn the multimeter from the resistance to capacitance measurement
mode. Proceed to verify the snubber capacitor by measuring from
the test point and the white wire at the 2-pole device snubber plug
(labeled snubber).
Snubber Test Point
White wire at
2-pole connector
Snubber Test Point
White wire at
2-pole connector
Figure 4.12 – Snubber Capacitance Test
To test the snubber capacitance, disconnect the plug of the self-
powered gate driver board labeled SHARING and SNUBBER. The
resistance between the white wire of the plug and the Test Point to its
left is the snubber capacitance.
Refer to Table 4.B to determine the appropriate snubber capacitance
value for the current rating of the SCR used. You should read the
actual snubber capacitor value shown in the table.
If the capacitor is found to be out of tolerance, refer to Chapter 6 –
Component Definition and Maintenance for detailed instructions on
how to replace the snubber capacitor.