7-26

Troubleshooting

7000L-UM300I-EN-P – June 2013

7000 “C” Frame

FAULT

MESSAGE

FAULT

CODE

DESCRIPTION

RECOMMENDED ACTIONS

2U1A Fbk FO Loss

267

PWM RECTIFIER SGCT FAULT

(Feedback Fiber-Optic Loss)

This fault will occur during the initial

contactor closure, the diagnostic sequence
after a start command, or the diagnostic

sequence after a stop command. The
rectifier monitors the state of the feedback
before a gate pulse is given, and monitors

the feedback after a gate pulse has been
sent. This fault occurs when the feedback
was low from the device before gating, and

is still low from the device after gating. The
drive then assumes the feedback must be

the problem.

The firmware now completes a diagnostics
sequence immediately after any drive reset,
with the goal of detecting faults before any

destructive action is taken from the next
action

– Verify that the Feedback Fiber-Optic

from the SCGT to the FOI board is not
damaged or disconnected

– Verify that the Gate Pulse has been

received by the SGCT board using
Gating Test Mode

– Complete a resistance check described

in Chapter 4, checking the devices,
sharing resistors, and snubber circuitry

– Replace all faulty components

2U1B Fbk FO Loss

273

2U1C Fbk FO Loss

324

2U4A Fbk FO Loss

270

2U4B Fbk FO Loss

276

2U4C Fbk FO Loss

327

2V3A Fbk FO Loss

269

2V3B Fbk FO Loss

275

2V3C Fbk FO Loss

326

2V6A Fbk FO Loss

272

2V6B Fbk FO Loss

278

2V6C Fbk FO Loss

329

2W2A Fbk FO Loss

268

2W2B Fbk FO Loss

274

2W2C Fbk FO Loss

325

2W5A Fbk FO Loss

271

2W5B Fbk FO Loss

277

2W5C Fbk FO Loss

328

2U1A Gat FO Loss

279

PWM RECTIFIER SGCT FAULT

(Gating Fiber-Optic Loss)

This fault will occur during the initial
contactor closure, the diagnostic sequence
after a start command, or the diagnostic
sequence after a stop command. The
rectifier monitors the state of the feedback
before a gate pulse is given, and monitors

the feedback after a gate pulse has been
sent. This fault occurs when the feedback

was high from the device before gating, and
is still high from the device after gating. The
drive then assumes the gating pulse must

not have reached the device.

The firmware now completes a diagnostics
sequence immediately after any drive reset,

with the goal of detecting faults before any
destructive action is taken from the next
action

– Check that the fiber optic cables are

seated properly in the Optical Interface
Board and the SCGT firing card

– Check that the fiber optic cable is not

pinched or damaged

– Complete a resistance check per the

instructions in the manual

– NOTE: SGCTs may not have completely

shorted, and still could read in the kΩ
range – Any devices with low suspect
readings should be changed

– Check the LED status of the SCGT gate

driver card for abnormal readings

– Complete a Gating Test mode check on

the devices

– Verify all the power connections to the

SCGT firing card are seated properly

2U1B Gat FO Loss

285

2U1C Gat FO Loss

330

2U4A Gat FO Loss

282

2U4B Gat FO Loss

288

2U4C Gat FO Loss

333

2V3A Gat FO Loss

281

2V3B Gat FO Loss

287

2V3C Gat FO Loss

332

2V6A Gat FO Loss

284

2V6B Gat FO Loss

290

2V6C Gat FO Loss

335

2W2A Gat FO Loss

280

2W2B Gat FO Loss

286

2W2C Gat FO Loss

331

2W5A Gat FO Loss

283

2W5B Gat FO Loss

289

2W5C Gat FO Loss

334