Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual

Page 121

Advertising
background image

Drive Installation 2-85

7000 “C” Frame

7000L-UM300I-EN-P – June 2013

Identification of Types of Electrical Supplies – Grounded and

Ungrounded Systems


When dealing with an ungrounded, three-phase electrical supply
system, the cable insulation must be capable of handling not only the
phase to phase voltage, but also the voltage to ground if one of the
other phases develops a ground fault. In practice, the cable insulation
of an ungrounded, three-phase system must be good for at least a
continuous voltage of root three (1.732) times the rated voltage of
the supply.


Ground Bus


The drive ground bus runs along the top of the drive at the front.
The ground bus is accessible at the top of each of the drive enclosures
when the enclosure door is opened (and the low voltage compartment
hinged out in the case of the incomer cabinet). It is the responsibility
of the installer to ensure that the drive is grounded properly, typically
at the point on the ground bus in the incomer cabinet, close to the
incoming power terminations.


Interlocking

Access to the medium voltage areas of the drive is restricted by the
use of key interlocking for safety.

At installation the key interlocking is set up so that access to the
medium voltage compartments of the equipment can only be made
when the upstream power is locked in the off position.

Additionally, the key interlocking prohibits the upstream power
being applied until the medium voltage drive’s access doors have
been closed and locked shut.

It is the responsibility of the installer to ensure that the key
interlocking is installed properly to the upstream equipment.

Advertising