7000 “C” Frame

7000L-UM300I-EN-P – June 2013


Logic Status Word – Database 3.001 and later

The following is the Logic Status word from the Drive.

It is common for all SCANport/DPI product specific peripherals.

Bit

Function

Value

Description

Notes

0

Ready

1

Drive is Ready

1

Running

1

Drive is Running

2

Commanded Direction

1

Drive has been commanded to run forward

0 = Reverse Command

3

Rotating Direction

1

Drive is rotating in the forward direction

0 = Reverse Rotation.

4

Accelerating

1

Drive is accelerating to commanded speed

0 = Drive is at speed

5

Decelerating

1

Drive is decelerating to commanded speed

0 = Drive is at speed or stopped

6

At Speed

1

Drive has reached the commanded speed

7

On Bypass

1

Motor is on bypass

0 = Motor connected to Drive

8

Reverse Enabled

1

The reverse command feature is enabled.

Changed in FRN 3.001 from
Reverse Disabled

9

Drive Fault

1

Drive has faulted

10

Drive Warning

1

Drive has encountered a warning

11

Local Lock

1

A DPI or XIO has local control of the drive

12

Forced Stop

1

A DPI adapter or CIB has forced the drive
to stop due to internal problems

15,13

Preset Speeds

0 0 0

External Reference 0 (Speed Pot)

0 0 1

External Reference 1 (Analog Input)

0 1 0

External Reference 2 (Current Loop Input)

0 1 1

Preset 1

1 0 0

Preset 2

1 0 1

Preset 3

1 1 0

Jog Preset

1 1 1

DPI Adapter Reference