3-58
Operator Interface
7000L-UM300I-EN-P – June 2013
7000 “C” Frame
Figure 3.80 – Diagnostic Setup
Figure 3.81 – Assign A Trace
From this screen, the tags to be monitored are assigned to a trace.
The tag which you assign to the first trace 'Trace 1' is used as the
trigger parameter. By default, when assigning a tag to Trace 1, the
trigger value (i.e. data) will be set to the tag's minimum value and
the trigger condition will be
'equal to'
. A tag must be assigned to
Trace 1 before the trigger value or condition can be set. From this
screen you may also set the interval between samples (i.e. Rate), and
the location of the trigger point within the view buffer. By default,
the trigger will occur in the middle of the buffer, however you may
change this by indicating the percentage of samples which will
follow (i.e. Post) the trigger point.
Assigning a Trace
To assign a tag to a trace, use the [cursor up] and [cursor down]
keys.
H
ighlight the desired trace and press the [enter] key. Since
there are more traces then can be seen on a single screen, use the
up/down arrow keys to extend the list to the additional traces on the
screen
. (If nothing happens then you have not gained the required
access to make changes. Press the [F8] key and refer to the section
entitled
Enter/Modify an Access Level to
gain access).