Rockwell Automation 7000L PowerFlex Medium Voltage AC Drive (C Frame) - Classic Control User Manual
Page 428

6-84
Component Definition and Maintenance
7000L-UM300I-EN-P – June 2013
7000 “C” Frame
LEDs
Green operational LED on front of unit detects DC FAIL output.
LED ON: outputs good
LED OFF: outputs bad
Terminal/connections descriptions
P1-DC input
PIN#
LABEL
DESCRIPTION ONLY
1
+56V
+56V input
2
+56V COMM
+56V common
3
EARTH
earth ground
P2-CONTROL
PIN#
LABEL
DESCRIPTION ONLY
1
XIO_PWR (+24V,3A)
+24V,3A/com5
2
XIOCOMM (com5)
0V/com5
P3-SPGDB
PIN#
LABEL
DESCRIPTION ONLY
1
SPGDBPWR (+15V,1A)
+15V,1A/com4
2
SPGDBPWR (+15V,1A)
+15V,1A/com4
3
SPGDBCOMM (com4)
0V/com4
4
SPGDBCOMM (com4)
0V/com4
P4-CIB
PIN#
LABEL
1
DC FAIL
2
DC WARNING
3
SPGDBFAIL
4
DC/DCFAILCOMM
5
EARTH
P5-SCBL
PIN#
LABEL
DESCRIPTION ONLY
1
+LEMPWR (+24V,1A)
+24V,1A/com2
2
LCOMM (com2)
0V/com2
3
–LEMPWR (-24V,1A)
-24V,1A/com2
4
+15V_PWR (+15V,1A)
+15V,1A/com1
5
ACOMM (com1)
0V/com1
6
–15V_PWR (-15V,1A)
-15V,1A/com1
7
+5V_PWR (+5V,10A)
+5V,10A/com1
8
DGND (com1)
0V/com1
9
+15V_ENC (+15V,1A)
+15V,1A/com3
10
ENC_COMM (com3)
0V/com3
11
DGND (com1)
0V/com1