Chapter 8

Installing NonĆstandard I/O

8-4

To install a 1785 PLC-5 processor in adapter mode, set the switches in
switch assembly SW2 as described here; set all other switches, including
the I/O chassis backplane switches as described in the 1785 PLC-5
Installation Manual
(1785-6.6.1).

Use switch assembly SW2 to set the I/O rack number and the number of
words to communicate. These switches are accessible from the bottom of
the module. Always set switch 1 to up (

Figure 8.3

).

Number of Words

Switch 2 determines the number of 16-bit words the scanner will write to
the PLC-5 processor and the number of words read from the PLC-5
processor. Set switch 2 as follows:

If switch 2 is set as:

Then the scanner writes and reads:

down

four words to and from the PLCĆ5 processor.

up

eight words to and from the PLCĆ5 processor.

I/O Rack Number

When a 1785 PLC-5 processor is used as an I/O adapter for the PLC-5/250
RS, it must be assigned an I/O rack number through which it is addressed
from the scanner. Switches 4 through 8 determine the I/O rack number
through which the 1785 PLC-5 controller is addressed by the scanner.

Starting I/O Number

Switch 3 determines the starting I/O group number. If the number of
words is 8, the starting I/O group must be number 0.

Setting 1785 PLCĆ5

Processor Switches