Installing the Modules
4-29
1.
Using the pin-outs in the table below, construct a cable depending
upon the type of device you are connecting. The OSI interface
module’s RS-232 port is configured as a DCE port.
RSĆ232C
Pin: Signal:
1
reserved. The reserved signals are for future use and shouldn't be wired to.
The OSI Interface's RSĆ232 port does not supply a shield connection.
2
TXD
3
RXD
4
reserved
5
signal ground
6
reserved
7
reserved
8
reserved
9
reserved
Figure 4.2
Pin Assignments for the 9ĆPin RSĆ232 Connector
5
4
3
2
1
9
8
7
6
RSĆ232 port
18394
Carrierband
module
Broadband
module
2.
If you want to use a shielded RS-232 cable, wire the shield:
at the other end of the cable or
via an RS-232 connector with a metal hood