Chapter 11

Checking the Hardware

11-4

If you

have a:

Check the LED

labeled:

It should be:

If it is not:

power

supply

DC OK

GREEN

make sure you turn on the power to the power supply.

cycle power by turning off the power from the power supply and then

turning it back on.

check fuses on the front of the power supply.

check ac wiring.

remove the module and make sure the voltageĆselector switch is set

to the correct operating voltage.

OVER TEMP

OFF

cycle power by turning off the power from the power supply and then

turn it back on.

make sure the fan is operating.

check the fan filter installation. Arrows on the filter should be pointing

upwards.

make sure there are no obstructions on the top or bottom of

the chassis.

make sure the power connector is secure.

make sure the filler plates are installed.

FAN STATUS

GREEN

make sure:

nothing is blocking the air flow on top of the chassis

the filter is inserted with the arrows pointing upwards

the filler plates are installed and secure

RM

PASS/FAIL

GREEN

make sure you turn on the power to the power supply.

EXECUTE

OFF

cycle power by turning off the power from the power supply and then

turning it back on.

at initial power up, clear memory or reĆdownload program.

OUTPUTS

OFF

FAULT

OFF

FORCES

OFF

CH 1

Flashing GREEN

(if connected)

make sure the connection is secure.

make sure there are no duplicate nodes.

make sure the blue and clear wires are not swapped.

CH 2

Flashing GREEN (if

configured as DH+ link)

CH 3

Flashing GREEN (if

configured as DH+ link)

MEM ERR

1

OFF

make sure the memory module is connected properly Ċ see appendix A.

BATT LOW

OFF

make sure the battery is inserted correctly in the battery holder.

RS2

PASS/FAIL

GREEN

cycle power by turning off the power from the power supply and then

turning it back on.

make sure you turn on the power to the power supply.

make sure the module is seated properly Ċ see appendix A.

CH 1

Flashing GREEN

(if connected)

make sure the connection is secure.

see RS5 on page

11Ć5

.

CH 2

Flashing GREEN

(if connected)

MEM ERR

1

OFF

make sure the memory module is connected properly Ċ see appendix A.

BATT LOW

OFF

make sure the battery is inserted correctly in the battery holder.

1

MEM ERR will be on at initial power up until memory is cleared or downloaded.