Chapter 11

Checking the Hardware

11-7

If you

have a:

If it is not:

It should be:

Check the LED

labeled:

1

MEM ERR will be on at initial power up until memory is cleared or downloaded.

2

These LEDs light after INTERCHANGE software has been loaded.

Ethernet

Interface

module

PASS/FAIL

GREEN

cycle power by turning off the power from the power supply and then

turning it back on.

make sure the module is seated properly Ċ see appendix A.

BACKPLANE

OFF

3

ENET

Flashing GREEN or off (If

connected and

communicating on the

Ethernet network)

make sure the connection to the Ethernet network is secure.

ERROR CODE

OFF

cycle power by turning off the power from the power supply and then

turning it back on.

make sure the module is seated properly Ċ see appendix A.

it will blink the error code. Call support services.

3

This LED lights after Network INTERCHANGE software has been loaded.

RM or KA Module on the Communication Link

Channel:

With this protocol:

LED should be:

CH 1

Master

Flashing GREEN

(when communication

Slave

(when communication

is occurring)

DF 1 (if another device is sending you messages and

you are replying)
DF 1 (If no other device is sending you messages)

OFF

Inactive

OFF

CH 2 and

DH link (and there's no other activity on the network)

GREEN

CH 3

DH link (and no messages are being sent to you on

the network)

OFF

DH link (and you are replying to messages from

another device on the network)

Flashing GREEN

Inactive

OFF

DH+ link

Flashing GREEN

If your configuration has I/O, your next step is to check it. To check I/O,
follow the steps below.

1.

Check the keying bands of each I/O module. Make sure they are
installed correctly. See chapter 7 in this manual if you’re unsure
about installing keying bands.

2.

Check the location and chassis positioning of each I/O module. Make
sure it is in its proper location (chassis, rack, and slot).

3.

Check the ac wiring on the I/O power supply.