What to do next – Rockwell Automation 5000,D50006.2.10 PI INSTALLATION MANUAL User Manual

Page 38

Advertising
background image

Chapter 3

Grounding the Components

3-4

Important: Make sure the scraped surface of the enclosure
wall is in contact with the total surface area of the ring terminal.

Enclosure wall

Scrape paint

Bolt

Scrape paint on enclosure wall

and use a star washer.

EquipmentĆgrounding

conductor

Star

washer

10020

Ground

lug

Nut

c.

Connect the grounding electrode conductor to your grounding
electrode system (earth ground potential). We recommend a
direct earth ground for maximum protection.

ATTENTION: Do not use an indirect earth ground,
such as a water pipe, building structure, or power distribution
system, otherwise your components may experience grounding
problems.

After you have grounded the components, go to chapter 4 to continue
installing your system.

What to do Next