Chapter 2

Mounting the Components

2-3

2.

Prepare the rack.

Mark the position of each component you will mount. Make sure the
holes line up with the holes of the mounting brackets.

Planned position of

component on rack

#10Ć32

Nominal

hole size

13220

3.

Mount a copper ground bus on the rack:

a.

Drill two clearance holes for #10-32 mounting screws in the
bus. Drill and tap a #10-32 hole for each component you will
attach to the rack.

Drilled and

tapped holes

Drilled clearance

holes for mounting

Distance on rack

17171

b.

Prepare a mounting location for the bus as indicated by the
mounting diagram and as you did in step 2.