Set the osi interface module pushwheel address, Connect the osi interface module – Rockwell Automation 5000,D50006.2.10 PI INSTALLATION MANUAL User Manual

Page 66

Advertising
background image

Chapter 4

Installing the Modules

4-28

Set the OSI Interface Module Pushwheel Address

Follow the steps below to set the OSI interface module’s pushwheel
address. If you have more than one OSI interface module in the same
chassis, set the pushwheels sequentially; make sure you set the first OSI
interface module’s pushwheel to 1.

1

1. Locate the pushwheel on the front panel of the

carrierband or broadband Interface modules

2. Set the pushwheel as indicated on the worksheet.

Setting the pushwheel:

To: Push the:

decrease the number

increase the number

top button

bottom button

18385

Connect the OSI Interface Module

The table below lists what you can connect to the OSI interface module.

You can connect the module to:

Using connector/port:

AĆB MAP Station Manager

(communicates locally as well as through the network)

carrierband or broadband

PLCĆ3

controller

PI system
ThirdĆparty device

Check the worksheet to see which connections to make. To connect to a
programming terminal running A-B MAP Station Manager software, see
chapter 5. To connect an RS-232 device, follow the steps below and see

Figure 4.2.