Set the configuration plug – Rockwell Automation 5000,D50006.2.10 PI INSTALLATION MANUAL User Manual
Page 97

Chapter 7
Installing 1771 I/O
7-9
3.
Set switches to define the first I/O group number. Use Table 7.B
Table 7.B
ExtendedĆLocal I/O Adapter Switch Settings, First I/O
Group Number
Set switch:
For First I/O Group Number:
7
8
0
on
on
2
on
off
4
off
on
6
off
off
Set the Configuration Plug
Use the configuration plug to specify whether you want to use 32-point
modules or 1771-IX and -IY modules in the chassis with the
extended-local I/O adapter module. If you are not using either one, the
plug may by left in either position.
Configuration Plug
17341
Do not place a jumper
on this set of pins.
1.
Lay the module on its
right side.
The configuration plugs
are visible on the lower
rear of the module.
2.
Set the configuration
plug as shown below
according to your
application.
If you are using:
But not:
Set configuration plug:
32-point I/O modules
and any address
method
1771-IX or 1771-IY
on the 2 lower pins
1771-IX and 1771-IY
modules and any
addressing method
32-point I/O modules
on the 2 upper pins