Chapter 7

Installing 1771 I/O

7-9

3.

Set switches to define the first I/O group number. Use Table 7.B

Table 7.B

ExtendedĆLocal I/O Adapter Switch Settings, First I/O

Group Number

Set switch:

For First I/O Group Number:

7

8

0

on

on

2

on

off

4

off

on

6

off

off

Set the Configuration Plug

Use the configuration plug to specify whether you want to use 32-point
modules or 1771-IX and -IY modules in the chassis with the
extended-local I/O adapter module. If you are not using either one, the
plug may by left in either position.

Configuration Plug

17341

Do not place a jumper

on this set of pins.

1.

Lay the module on its

right side.

The configuration plugs

are visible on the lower

rear of the module.

2.

Set the configuration

plug as shown below

according to your

application.

If you are using:

But not:

Set configuration plug:

32-point I/O modules

and any address

method

1771-IX or 1771-IY

on the 2 lower pins

1771-IX and 1771-IY

modules and any

addressing method

32-point I/O modules

on the 2 upper pins