Chapter 4

Installing the Modules

4-33

Specify Switch Settings on the OSI Carrierband/Broadband

Interface Module

Switch: Position:

Description:

1

up

if there is a valid image in nonĆvolatile memory, the OSI interface module will enter fully operational

mode after:

a power cycle, regardless of the mode preceding the power cycle

you enter a reset command from the AĆB MAP Station Manager, regardless of the mode

preceding the reset

you enter a change mode to Fully Operational from the AĆB MAP Station Manager

if there is not a valid image in nonĆvolatile memory, the OSI interface module will not enter fully

operational mode but will enter Partially Operational mode.

down

the OSI interface module will enter partially operational mode after:

a power cycle, regardless of the mode preceding the power cycle

you enter a reset command from the AĆB MAP Station Manager, regardless of the mode

preceding the reset

you enter a change mode to Partially Operational from the AĆB MAP Station Manager

2

up

the OSI interface module uses user defaults, if available, at powerĆup or reset (see the PI OSI Interface

Software User's Manual for a list of user defaults). If user defaults aren't available, the interface will

use AĆB communication defaults.

down

the OSI interface module uses AĆB communication defaults at powerĆup or reset.

3

preset at AĆB

reserved (do not change)

4

preset at AĆB

reserved (do not change)

Important: Keep switches 3 and 4 in the up position; otherwise, the PI system stays in a power cycle.