Table 4.E
Configure Termination Resistors for the RS2
If the transmission rate is:
And the scanner is physically located: Then put the internal 150ĆOhm
terminationĆresistor jumper in the:
57.6k bit/s or 115k bit/s
middle of remote I/O link
out position
end of remote I/O link
in position
230k bit/s
middle of remote I/O link
out position
end of remote I/O link
out position, and attach 82ĆOhm termination
resistor between pins 2 and 3
Figure 4.1
RS2 Internal 150ĆOhm Termination Resistors
(Front)
Module
Memory module
RS2 (internal 150ĆOhm termination resistor)
17085
Termination
Resistor
CH JMPR
IN
OUT
1
E1
3 2 1
3 2 1
2
E2
3 2 1
3 2 1
Install the RS
Install the module as shown in appendix A.