Fan assembly, Connecting i/o power supplies, 10ć4 – Rockwell Automation 5000,D50006.2.10 PI INSTALLATION MANUAL User Manual

Page 127: Fan assembly connecting i/o power supplies

Advertising
background image

Chapter 10

Connecting ac Power

10-4

You connect the fan assembly to ac power. The input ranges for the fan
assembly are:

85 to 132Vac for 110/120V ac
170 to 264Vac for 220V ac
47 to 63 Hz

To connect the fan assembly to ac power, follow the steps below.

1. Use a 1/8" (3.1mm) wide blade, insulated handled

screwdriver to set the voltage switch to the

operating voltage of your system (it is shipped set

to 200V ac and can be changed to 100/120V ac).

2. Wire the line voltage

connector as shown.

3. Attach the wired connector to the female

connector labeled GND L2/N L1 on the

fan chassis.

4. Attach the other end of the wires to ac power

as shown in your system designer

wiring diagrams.

EQPT/GND

L1

L2/N

16797

100/120 AC

200V AC

Install each power supply for each I/O chassis as described in the
publication shipped with each power supply.

Fan Assembly

Connecting I/O Power Supplies

Advertising