Connect to interlock relay, Connect to line voltage – Rockwell Automation 5000,D50006.2.10 PI INSTALLATION MANUAL User Manual
Page 45

Chapter 4
Installing the Modules
4-7
3.
Connect the 5120-CP2 cable to the fan chassis, the power supply
and a 24V external power supply.
5120ĆCP2
a. Connect the spade lugs to
an external 24V power supply.
b. Connect the rightĆangle
connector of the 5120ĆCP2
cable to the port labeled FAN
CHASSIS on the power supply.
c. Route the cable away from
the Interlock Relay and Line
Voltage connectors.
d. Connect the straight end of
the cable to the port labeled
FAN STATUS CABLE on the
fan chassis.
Connect triple red to +.
Connect triple
black to -.
Connect single red
to + sense or +.
Connect single black
to - sense or -.
19786
4.
Connect the 5120-CP3 cable to a 24V external power supply.
Connect triple red to +.
Connect triple
black to -.
Connect single red
to + sense or +.
Connect single black
to - sense or -.
5120ĆCP3
a. Connect the spade lugs
to an external 24V power
supply.
b. Connect the rightĆangle
connector of the 5120ĆCP3
cable to the port labled
FAN CHASSIS on the
power supply.
c. Route the cable away
from the Interlock Relay
and Line Voltage
connectors.
19787
Connect to Interlock Relay
See chapter 9 to connect the interlock relay.
Connect to Line Voltage
See chapter 10 to connect ac power.