Chapter 11

Checking the Hardware

11-5

If you

have a:

If it is not:

It should be:

Check the LED

labeled:

RS5

PASS/FAIL

GREEN

cycle power by turning off the power from the power supply and then

turning it back on.

make sure the module is seated properly Ċ see appendix A.

CH 1

GREEN (if configured

and connected)

make sure the connection is secure.

make sure there are no duplicate or overlapping rack

numbers assigned.

make sure that the rack is configured for a rack address in the range

defined by the scanner pushwheels.

CH 2

Flashing GREEN (if

configured but some

adapters faulted or

disconnected)

CH 3

Flashing RED (if

configured but all

adapters faulted or

disconnected)

CH 4

OFF (if not configured)

CH 5
ERROR

OFF

note flashing error code.

cycle power by turning off the power from the power supply and then

turning it back on.

BATT LOW

OFF

make sure the battery is inserted correctly in the battery holder.

LP

PASS/FAIL

GREEN

cycle power by turning off the power from the power supply and then

turning it back on.

make sure the pushwheel number is correct.

make sure the module is seated properly Ċ see appendix A.

MEM ERR

1

OFF

make sure the memory module is connected properly Ċ see appendix A.

BATT LOW

OFF

make sure the battery is inserted correctly in the battery holder.

CVIM

module

PASS/FAIL

GREEN

make sure the module is seated properly Ċ see appendix A.

make sure you turn on the power to the power supply

module

TRIGGER 1

OFF

make sure you turn on the power to the power supply.

TRIGGER 2

OFF

MEMORY

OFF

MicroVAX

Information

Processor

module EP

PASS/FAIL

GREEN

cycle power by turning off the power from the power supply and then

turning it back on.

make sure the module is seated properly Ċ see appendix A.

module EP

or EE

ENET

Flashing GREEN (If

connected and

communicating on the

Ethernet network)

make sure the connection to the Ethernet network is secure.

PROCESSOR

OFF

2

BACKPLANE

OFF

2

ERROR

OFF

cycle power by turning off the power from the power supply and then

turning it back on.

make sure the module is seated properly Ċ see appendix A.

it will blink the error code. Call support services.

BATTERY LOW

OFF

make sure the battery is inserted correctly in the battery holder.