Rockwell Automation 5000,D50006.2.10 PI INSTALLATION MANUAL User Manual
Page 55
![background image](/manuals/580790/55/background.png)
Chapter 4
Installing the Modules
4-17
Install the Battery
To install the RS battery, see “Install the Battery” section on page
for instruction.
Set the RS Module Address
Follow the steps below to set the RS module address. For RS2, the address
must start at 1 for the first RS and be consecutive for the other RS modules
up to 4.
For RS5, the address can be spread among the RS modules, or all four
addresses may be used on one RS5. The addresses must be consecutive.
RS5
1. Locate the pushwheel on the front panel of the RS.
2. Set the pushwheel as indicated on the worksheet.
Setting the pushwheel:
To: Push the:
decrease the number
increase the number
top button
bottom button
19788
1
4
Connect I/O
To connect remote I/O to the ports labeled CH 1 to CH 4, and local I/O to
CH5, see chapter 7.
The RS5 pushwheels:
Is equivalent to:
1Ć4
four RS2 modules' pushwheels.
1Ć1
one RS2 module's pushwheel.