Checking Module Indicator Lights

Use the following table to check the module indicator lights.

Check the LED labeled:

1

It should be:

If it is not:

PASS/FAIL

GREEN

cycle power by turning off the power from the power supply

and then turning it back on.

make sure the module is seated properly, see appendix A.

ENET A

2

or ENET

Flashing GREEN

(If connected and

communicating on

Ethernet)

make sure the Ethernet connection is secure.

PROCESSOR

OFF

1

BACKPLANE

OFF

1

ERROR

OFF

cycle power by turning off the power from the power supply

and then turn it back on.

make sure the module is seated properly Ċ see

appendix A.

note the blinking error code; count the flashes between

pauses and be prepared to give that information to

support services.

BATTERY LOW

OFF

Make sure the battery is inserted correctly in the battery holder.

1

These LEDs light after Interchange software has been loaded.

2

ENET A is for the MicroVAX Information Processor and ENET is for the MicroVAX Information Processor EP or EE.

Connecting the Program Loader

If you are using the program loader (series A or B), you should have
already connected it to the module. Make sure you have rebooted the
system at least once since the program loader was connected, or the
MicroVAX Information Processor will not recognize that the program
loader is connected. See the Program Loader Installation Data
(5000-2.93) for more information.

Setting Up the Terminal

To set up the console terminal, complete the following steps:

1.

Attach the terminal to port 3 (OPA0) on the distribution panel.

2.

Set the terminal to:

9600 baud
transmit = receive
8 bits
no parity
1 stop bit
no local echo